§215.TABLE A. Rate of Discharge  


Latest version.
  • Minimum required rate of discharge in cubic feet per minute (CFM) of air for safety relief valves.  Discharge measured at 60 degrees F. and atmospheric pressure (14.7 pounds per square inch).

     

    Surface Area Sq. Ft.

    CFM

    Surface Area Sq. Ft.

    CFM

    Surface Area Sq. Ft.

    CFM

     

     

     

     

     

     

    20

    258

    185

    1,600

    900

    5,850

    25

    310

    190

    1,640

    950

    6,120

    30

    360

    195

    1,670

    1,000

    6,380

    35

    408

    200

    1,710

    1,050

    6,640

    40

    455

    210

    1,780

    1,100

    6,900

    45

    501

    220

    1,850

    1,150

    7,160

    50

    547

    230

    1,920

    1,200

    7,410

    55

    591

    240

    1,980

    1,250

    7,660

    60

    635

    250

    2,050

    1,300

    7,910

    65

    678

    260

    2,120

    1,350

    8,160

    70

    720

    270

    2,180

    1,400

    8,410

    75

    762

    280

    2,250

    1,450

    8,650

    80

    804

    290

    2,320

    1,500

    8,900

    85

    845

    300

    2,380

    1,550

    9,140

    90

    885

    310

    2,450

    1,600

    9,380

    95

    925

    320

    2,510

    1,650

    9,620

    100

    965

    330

    2,570

    1,700

    9,860

    105

    1,010

    340

    2,640

    1,750

    10,090

    110

    1,050

    350

    2,700

    1,800

    10,330

    115

    1,090

    360

    2,760

    1,850

    10,560

    120

    1,120

    370

    2,830

    1,900

    10,800

    125

    1,160

    380

    2,890

    1,950

    11,030

    130

    1,200

    390

    2,950

    2,000

    11,260

    135

    1,240

    400

    3,010

    2,050

    11,490

    140

    1,280

    450

    3,320

    2,100

    11,720

    145

    1,310

    500

    3,620

    2,150

    11,950

    150

    1,350

    550

    3,910

    2,200

    12,180

    155

    1,390

    600

    4,200

    2,250

    12,400

    160

    1,420

    650

    4,480

    2,300

    12,630

    165

    1,460

    700

    4,760

    2,350

    12,850

    170

    1,500

    750

    5,040

    2,400

    13,080

    175

    1,530

    800

    5,300

    2,450

    13,300

    180

    1,570

    850

    5,590

    2,500

    13,520

     

    Surface area = Total outside surface area of container in square feet. When the surface area is not stamped on the name plate or when the marking is not legible, the area can be calculated by using one of the following formulas:

     

    a)         Cylindrical container with hemispherical heads area = (overall length in feet times outside diameter in feet times 3.1416)

    b)         Cylindrical container with semi-ellipsoidal heads. Area = (overall length in feet plus 0.3 outside diameter in feet) times diameter in feet times 3.1416.

    c)         Spherical Container. Area = Outside diameter in feet squared times 3.1416

     

    Flow Rate SCFM Air = cubic feet per minute of air required at standard conditions, 60 degrees F. and atmospheric pressure (14.7 psia).

     

    The rate of discharge may be interpolated for intermediate values of surface area.  For container with total outside surface area greater than 2,000 sq. ft., the required flow rate can be calculated using the formula, Flow Rate SCFM Air = 22.11A degrees .82, where A= outside surface area of the container in square feet.