Illinois Administrative Code (Last Updated: March 27, 2024) |
TITLE8. AGRICULTURE AND ANIMALS |
PART215. ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS, EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES |
SUBPARTB. NITROGEN FERTILIZER SOLUTIONS |
§215.TABLE A. Rate of Discharge
-
Minimum required rate of discharge in cubic feet per minute (CFM) of air for safety relief valves. Discharge measured at 60 degrees F. and atmospheric pressure (14.7 pounds per square inch).
Surface Area Sq. Ft.
CFM
Surface Area Sq. Ft.
CFM
Surface Area Sq. Ft.
CFM
20
258
185
1,600
900
5,850
25
310
190
1,640
950
6,120
30
360
195
1,670
1,000
6,380
35
408
200
1,710
1,050
6,640
40
455
210
1,780
1,100
6,900
45
501
220
1,850
1,150
7,160
50
547
230
1,920
1,200
7,410
55
591
240
1,980
1,250
7,660
60
635
250
2,050
1,300
7,910
65
678
260
2,120
1,350
8,160
70
720
270
2,180
1,400
8,410
75
762
280
2,250
1,450
8,650
80
804
290
2,320
1,500
8,900
85
845
300
2,380
1,550
9,140
90
885
310
2,450
1,600
9,380
95
925
320
2,510
1,650
9,620
100
965
330
2,570
1,700
9,860
105
1,010
340
2,640
1,750
10,090
110
1,050
350
2,700
1,800
10,330
115
1,090
360
2,760
1,850
10,560
120
1,120
370
2,830
1,900
10,800
125
1,160
380
2,890
1,950
11,030
130
1,200
390
2,950
2,000
11,260
135
1,240
400
3,010
2,050
11,490
140
1,280
450
3,320
2,100
11,720
145
1,310
500
3,620
2,150
11,950
150
1,350
550
3,910
2,200
12,180
155
1,390
600
4,200
2,250
12,400
160
1,420
650
4,480
2,300
12,630
165
1,460
700
4,760
2,350
12,850
170
1,500
750
5,040
2,400
13,080
175
1,530
800
5,300
2,450
13,300
180
1,570
850
5,590
2,500
13,520
Surface area = Total outside surface area of container in square feet. When the surface area is not stamped on the name plate or when the marking is not legible, the area can be calculated by using one of the following formulas:
a) Cylindrical container with hemispherical heads area = (overall length in feet times outside diameter in feet times 3.1416)
b) Cylindrical container with semi-ellipsoidal heads. Area = (overall length in feet plus 0.3 outside diameter in feet) times diameter in feet times 3.1416.
c) Spherical Container. Area = Outside diameter in feet squared times 3.1416
Flow Rate SCFM Air = cubic feet per minute of air required at standard conditions, 60 degrees F. and atmospheric pressure (14.7 psia).
The rate of discharge may be interpolated for intermediate values of surface area. For container with total outside surface area greater than 2,000 sq. ft., the required flow rate can be calculated using the formula, Flow Rate SCFM Air = 22.11A degrees .82, where A= outside surface area of the container in square feet.