Illinois Administrative Code (Last Updated: March 27, 2024) |
TITLE77. PUBLIC HEALTH |
PART920. WATER WELL CONSTRUCTION CODE |
§920.ILLUSTRATION A. Unconsolidated Formations: Oversized Drill Hole
Latest version.
-
1. Diameter of drill hole must be 3" larger than the outer diameter of the casing or coupling, whichever is greater.
2. Casing must extend a minimum of 20'.
3. Annular space that exists between hole and casing must be filled with bentonite grout or neat cement grout within a maximum of 10 feet of the top of the screen to finished ground surface.
.
(Source: Amended at 37 Ill. Reg. 19676, effective November 25, 2013)