§900.TABLE A. Sources of Pollution in Location to Wells and/or Finished Water Storage Facilities  


Latest version.
  •  

     

    Source of Pollution

    Minimum Distance in Feet

     

     

    Cesspools

    150

    Leaching Pit

    100

    Pit Privy

     75

    Subsurface Seepage Tile

     75

    Manure Piles

     75

    Septic Tank

     50

    Barnyard

     50

    Sewers

     50

    Footing Drainings (no connections to

     

      a sewer or sump handling sewage)

     10

    Pump House Floor Drain (cast-iron

     

      with watertight joint and having

     

      free fall discharge to ground

     

      surface)

      2

    Lakes, Ponds, or Streams

     25

     

     

    NOTE:  Distances listed above apply only in clay and loam soils.  In

     

    gravel and sand formations safe distances will be variable, being greater

     

    than for clay and loam soils.  The necessary minimum distances listed will

     

    depend upon ground surface conditions, depth of water table, the location

     

    of sources of contamination and the ability of the soil to remove bacteria.