Illinois Administrative Code (Last Updated: March 27, 2024) |
TITLE41. FIRE PROTECTION |
PART200. STORAGE, TRANSPORTATION, SALE, AND USE OF LIQUEFIED PETROLEUM GAS |
§200.10. Storage and Handling of Liquefied Petroleum Gases
Latest version.
-
Requirements for the storage and handling of liquefied petroleum gases as contained in the 2011 Edition of NFPA 58 (Liquefied Petroleum Gas Code) are mandatory with the following additional requirements: The pressure relief valve discharge on each aboveground container of more than 2000 gal. water capacity shall be piped vertically upward to a point at least 7 ft. above the top of the container, and the discharge opening shall be unobstructed to the open air.