§229.APPENDIX B. Operating Parameters to be Monitored and Minimum Measurement and Recording Frequencies  


Latest version.
  • An "X" in any box in this matrix means that measurement of that parameter is required.

     

    MINIMUM FREQUENCY

    CONTROL SYSTEM

    Operating Parameters

    Data Measurement

    Data Recording

    Dry Scrubber Followed by Fabric Filter

    Wet Scrubber

    Dry Scrubber Followed by Fabric Filter and Wet Scrubber

    Selective Noncatalytic Reduction System

    Maximum Charge Rate1

    Continuous

    Once per hour

    X

    X

    X

    X

    Maximum Fabric Filter Inlet Temperature

    Continuous

    Once per minute

    X

     

    X

     

    Maximum Flue Gas Temperature

    Continuous

    Once per minute

    X

    X

     

     

    Minimum Secondary Chamber Temperature

    Continuous

    Once per minute

    X

    X

    X

    X

    Minimum Dioxin/Furan Sorbent Flow Rate

    Hourly

    Once per hour

    X

     

    X

     

    Minimum HCl Sorbent Flow Rate

    Hourly

    Once per hour

    X

     

    X

     

    Minimum Reagent Flow Rate

    Hourly

    Once per hour

     

     

     

    X

    Minimum Hg Sorbent Flow Rate

    Hourly

    Once per hour

    X

     

    X

     

    Minimum Pressure Drop Across the Wet Scrubber or Minimum Horsepower or Amperage to Wet Scrubber

    Continuous

    Once per minute

     

    X

    X

     

    Minimum Scrubber Liquor Flow Rate

    Continuous

    Once per hour

     

    X

    X

     

    Minimum Scrubber Liquor pH

    Continuous

    Once per hour

     

    X

    X

     

    1For batch HMIWIs, record the charge per batch.

     

    (Source:  Amended at 35 Ill. Reg. 16615, effective September 30, 2011)