Illinois Administrative Code (Last Updated: March 27, 2024) |
TITLE35. ENVIRONMENTAL PROTECTION |
PART229. HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS |
SUBPARTL. RECORDKEEPING AND REPORTING REQUIREMENTS |
§229.APPENDIX B. Operating Parameters to be Monitored and Minimum Measurement and Recording Frequencies
-
An "X" in any box in this matrix means that measurement of that parameter is required.
MINIMUM FREQUENCY
CONTROL SYSTEM
Operating Parameters
Data Measurement
Data Recording
Dry Scrubber Followed by Fabric Filter
Wet Scrubber
Dry Scrubber Followed by Fabric Filter and Wet Scrubber
Selective Noncatalytic Reduction System
Maximum Charge Rate1
Continuous
Once per hour
X
X
X
X
Maximum Fabric Filter Inlet Temperature
Continuous
Once per minute
X
X
Maximum Flue Gas Temperature
Continuous
Once per minute
X
X
Minimum Secondary Chamber Temperature
Continuous
Once per minute
X
X
X
X
Minimum Dioxin/Furan Sorbent Flow Rate
Hourly
Once per hour
X
X
Minimum HCl Sorbent Flow Rate
Hourly
Once per hour
X
X
Minimum Reagent Flow Rate
Hourly
Once per hour
X
Minimum Hg Sorbent Flow Rate
Hourly
Once per hour
X
X
Minimum Pressure Drop Across the Wet Scrubber or Minimum Horsepower or Amperage to Wet Scrubber
Continuous
Once per minute
X
X
Minimum Scrubber Liquor Flow Rate
Continuous
Once per hour
X
X
Minimum Scrubber Liquor pH
Continuous
Once per hour
X
X
1For batch HMIWIs, record the charge per batch.
(Source: Amended at 35 Ill. Reg. 16615, effective September 30, 2011)