§218.488. Monitoring for Air Pollution Control Equipment  


Latest version.
  • a)         At a minimum, continuous monitors for the following parameters shall be installed on air pollution control equipment used to control sources subject to this Subpart:

     

    1)         Destruction device combustion temperature.

     

    2)         Temperature rise across a catalytic afterburner bed.

     

    3)         VOM concentration on a carbon adsorption unit to determine breakthrough.

     

    4)         Outlet gas temperature of a refrigerated condenser.

     

    5)         Temperature of a non-refrigerated condenser coolant supply system.

     

    b)         Each monitor shall be equipped with a recording device.

     

    c)         Each monitor shall be calibrated quarterly.

     

    d)         Each monitor shall operate at all times while the associated control equipment is operating.